AACORE SUPPLY · HVAC & REFRIGERATION[email protected]
Enquiry 0
BOCK · Compresores alternativos

HGX34/170-4 ML CO2 T

Technical data

Compresores alternativos

Model
HGX34/170-4 ML CO2 T
Displacement 50/60 Hz (1450/1740 ¹/min)
14,50 / 17,40 m³/h
Electrical supply
Electrical supply to be confirmed from the nameplate.

Before confirming, check the nameplate and serial number.

Additional technical information

Model
HGX34/170-4 ML CO2 T
Family
HG · CO₂ transcrítico
Number of cylinders / Bore / Stroke
4 / 34 mm / 46 mm
Voltage 1)
380-420V Y/YY -3- 50Hz PW
Winding divided into
50% / 50%
Max. working current 2)
35.3 A
Max. power consumption 2)
21.4 kW
Starting current (rotor blocked) 2)
101.0 / 174.0 A
Motor protection
INT69 G
Protection terminal box
IP 66
Weight
199 kg
Frequency range 3)
20 - 70 Hz
Max. permissible overpressure (g) (LP/HP) 4)
100 / 150 bar
Connection suction line SV
28 mm - 1 1/8 "
Connection discharge line DV
22 mm - 7/8 "
Lubrication
Oil pump
Oil type R744
BOCKlub E85
Oil charge
2,3 Ltr.
Dimensions Length / Width / Height
711 / 421 / 393 mm
Sound power level L WA 5)
76 dB(A) @ -10 °C / 15 °C / 10 K
Sound pressure level L pA 5)
63 dB(A) @ -10 °C / 15 °C / 10 K
Voltage
400 V

Documentation

Dimensions and connections drawing · BOCK · 16238-web (PDF)Exploded drawing and spare part positions · BOCK · 16238-3 (PDF)Assembly instructions HGX34 CO2 T · BOCK · 96459-11-2022-d (PDF)Assembly instructions HGX34 CO2 T · BOCK · 96459-05-2022-gb (PDF)CO2 compressors · BOCK · danfoss-bock-co-compressor-program (PDF)CO2 compressors · BOCK · bock (PDF)Protection module manual INT69 G · BOCK · 96333-int69-g-d-01-2021 (PDF)Protection module manual INT69 G · BOCK · 96333-int69-g-gb-01-2021 (PDF)Protection module manual INT69 G · BOCK · 96333-int69-g-f-01-2021 (PDF)Protection module manual INT69 G · BOCK · 96333-int69-g-i-01-2021 (PDF)Protection module manual INT69 G · BOCK · 96333-int69-g-e-01-2021 (PDF)Protection module manual INT69 G · BOCK · 96333-int69-g-ru-01-2021 (PDF)Capacity regulator flexxCO2NTROL DCR22 CO2 · BOCK · 96590-07-2025-d (PDF)Capacity regulator flexxCO2NTROL DCR22 CO2 · BOCK · 96590-07-2025-gb (PDF)Electric motor repair instructions HGX CO2 T · BOCK · 09430-06-2021-d (PDF)Electric motor repair instructions HGX CO2 T · BOCK · 09430-06-2021-gb (PDF)Maximum permissible inclination of BOCK compressors · BOCK · 96301-09-2021-dgbf (PDF)Oil differential pressure sensor ΔP II · BOCK · 96038-01-2021-dgbf (PDF)Oil level Regulators COM · BOCK · oil-level-regulators-com-ai464641146309en-000101 (PDF)Sound pressure level and sound power levell for HGX CO2 and HRX40 CO2T with R744 · BOCK · 96413-11-2025-dgb (PDF)EU RoHS declaration of conformity · BOCK · 96601-01-2025-dgbf (PDF)REACH Regulation · BOCK · 96584-11-2023-dgbf (PDF)Official BOCK spare parts list · HGX34/170-4 ML CO2 T